Effect of helix number on the thermohydraulic performance of a cross flow heat exchanger: experimental and numerical study


Yoladi M., KOTCİOĞLU İ., Akyurek E. F.

Journal of the Brazilian Society of Mechanical Sciences and Engineering, cilt.48, sa.12, 2026 (SCI-Expanded, Scopus)

  • Yayın Türü: Makale / Tam Makale
  • Cilt numarası: 48 Sayı: 12
  • Basım Tarihi: 2026
  • Doi Numarası: 10.1007/s40430-026-06805-9
  • Dergi Adı: Journal of the Brazilian Society of Mechanical Sciences and Engineering
  • Derginin Tarandığı İndeksler: Science Citation Index Expanded (SCI-EXPANDED), Scopus, Aerospace Database, Compendex, INSPEC, Materials Science & Engineering Collection (ProQuest), Technology Collection (ProQuest)
  • Anahtar Kelimeler: Cross-flow heat exchanger, Helical fin, Thermohydraulic performance, Experimental investigation, CFD, ANSYS Fluent
  • Atatürk Üniversitesi Adresli: Evet

Özet

The thermo hydraulic performance of single helix, double helix, triple helix fin geometries were experimentally and numerically investigated for constructing a cross-flow heat exchanger. In the experiment, the effect of different spiral geometries on heat transfer enhancement and pressure drop due to friction was investigated. Based on the test results, the thermohydraulic performance was numerically calculated at a constant operating condition (air inlet temperature: 47 °C, water mass flow rate: 12 g/s, air velocity: 4.8 m/s) using ANSYS Fluent and ANSYS Discovery. Experimentally, the average Nusselt number (Nu) and the average overall heat transfer coefficient (U) increased with an increase in the number of helix. The average Nu and U for the single, double, triple helix geometry were 165.8, 182.8 and 190.4, and 143.5, 160.7 and 168.7 W/m2K, respectively. The average friction factor (f) for the single, double, triple helix geometry were 0.2315, 0.2313 and 0.2241. Thus, the ratio of the increase in Nu and U for the triple helix to those of single helix was 14.81% and 17.61%, respectively, and the friction factor decreased by 3.18%. The results obtained by using Discovery and Fluent for the numerical calculations were consistent with the experimental results, and showed that the ratio of the decrease in the pressure drop for triple helix to single helix was 23.76%, and the outlet temperature decreased by approximately 1.6 °C. The ratio of the decrease in the pressure drop for the triple helix geometry in terms of the same configuration was 10.14%. The results revealed that triple helix geometry shows an improved flow distribution, enhanced interaction and better thermohydraulic performance. Hence, for the above test conditions, the triple helix fin geometry is the most suitable configuration for a cross-flow heat exchanger. The specific effect of the helix number, rather than the fin shape or density alone, was isolated, and the triple helix configuration achieved the highest Performance Evaluation Criterion (PEC = 1.16) while maintaining a comparable friction factor level.